Powerstac Library: “SIG” Wire Combinations

When the SIG option is selected (providing an independent conductor for each circuit), more room will be needed to accommodate the additional wiring. Therefore the largest J-box or non-metallic conduit will be used, which may differ from your original selection. Note that this J-box may need to be externally mounted to the rack.

Module Size (inches) Allowable Wire Combinations

SIG option with
J-box No. 5
6 x 6 x 4 15 (15A or 20A circuits) + 0 (30A circuits)
14 (15A or 20A circuits) + 1 (30A circuits)
13 (15A or 20A circuits) + 2 (30A circuits)
12 (15A or 20A circuits) + 3 (30A circuits)
11 (15A or 20A circuits) + 4 (30A circuits)
10 (15A or 20A circuits) + 5 (30A circuits)
9 (15A or 20A circuits) + 6 (30A circuits)
7 (15A or 20A circuits) + 7 (30A circuits)
6 (15A or 20A circuits) + 8 (30A circuits)
5 (15A or 20A circuits) + 9 (30A circuits)
4 (15A or 20A circuits) + 10 (30A circuits)
3 (15A or 20A circuits) + 11 (30A circuits)
2 (15A or 20A circuits) + 12 (30A circuits)
1 (15A or 20A circuits) + 13 (30A circuits)
0 (1A5 or 20A circuits) + 14 (30A circuits)

SIG option with
non-metallic flexible conduit
1.25 dia. 15 (20A circuits) + 0 (30A circuits)
14 (20A circuits) + 0 (30A circuits)
13 (20A circuits) + 1 (30A circuits)
12 (20A circuits) + 1 (30A circuits)
11 (20A circuits) + 2 (30A circuits)
10 (20A circuits) + 3 (30A circuits)
9 (20A circuits) + 3 (30A circuits)
8 (20A circuits) + 4 (30A circuits)
7 (20A circuits) + 5 (30A circuits)
6 (20A circuits) + 5 (30A circuits)
5 (20A circuits) + 6 (30A circuits)
4 (20A circuits) + 6 (30A circuits)
3 (20A circuits) + 7 (30A circuits)
2 (20A circuits) + 8 (30A circuits)
1 (20A circuits) + 8 (30A circuits)
0 (20A circuits) + 9 (30A circuits)